Блок контроля PMC-530A
Обзор
| Technical Parameters |
Index |
|
| Accuracy class |
U, I, F is 0.2, P, Q of 0.5, active power of 0.5, reactive power as a |
|
| Display method |
LCD / LED switch or cycle (programmable) |
|
| power supply |
Scope of work |
AC, DC 85V ~ 265V |
| Power consumption |
5VA |
|
| Lose Enter Measure the amount |
The internet |
Phase three-wire, three-phase four-wire |
| RATINGS |
Voltage: AC100V, 400V; current: AC1A, 5A (when ordering indicate voltage, current ratio) |
|
| Overload |
Duration: 1.2 times the instantaneous: voltage 2 times (10 seconds), the current 10 times (5 seconds) |
|
| Power consumption |
Voltage circuit power consumption<1VA (per phase) Current circuit power consumption<0.4VA (per phase) |
|
| Impedance |
Voltage circuit impedance> 200k; current loop impedance<20m |
|
| Frequency |
50Hz 10% |
|
| Energy Metering |
Positive and negative active and reactive energy metering |
|
| Extensions |
Digital Communication Interface |
RS-485 interface standard way, MODBUS-RTU statute; optional PROFIBUS-DP interface or CANBUS Interface |
| Pulse output (standard) |
2-way power pulse output (open collector optocoupler output) |
|
| Analog output (optional) |
4 DC 4 ~ 20mA analog transmit output (LCD Table 6 square table and 1 output) |
|
| Digital input (optional) |
4 digital inputs, dry contact way |
|
| Switching output (optional) |
4-way normally open contact relay output (LCD table and 6 square table 2 outputs), Relay contact capacity: AC220V / 5A |
|
| working environment |
-10 ~ 60 , relative humidity 93%, non-corrosive gases Altitude 2500m |
|
| Isolation voltage |
Power / input / output voltage between>2kV |
|
| Dimensions |
42 Square: 120 × 120 × 84mm; 96 square: 96 × 96 × 100mm; 6 square: 83 × 83 × 92mm |
|
| Hole Size |
2 (42 square): 111 × 111mm; 9 (96 square): 91 × 91mm; 3 (6 squares): 76 × 76mm |
|
Оставьте отзыв об этом товаре первым!